Telecommunications

Guidelines for Support Structures

For Circuit Installation

Requirements for circuit delivery are as follows:

  1. 2" to 4" Schedule 40 PVC or metallic conduit(s) from the property line to the building(s).
  2. A closet or equipment room to locate telecom equipment. Floorspace requirements vary depending on the size and characteristics of the building.
  3. One or more 120VAC power outlets. Some buildings may require 240VAC.
  4. 4' X 8' X 3/4" plywood backboard(s)
  5. Conduit, ceiling space, under floor duct or other type of enclosed raceway from equipment rooms to tenant spaces.
  6. 4" riser sleeves between floors of a multi-story building. Firestop material to be installed after cable placement.
  7. #6 AWG insulated wire from the building's grounding electrode system. Larger diameter wire may be needed in some cases.

 

Note: If your services are being extended from the circuit to a suite, a pull string is required.